Assembling:
To mount the connector permanently, it is necessary to press it by means of the press with well-selected jaws.
Ends of sector conductors must be transformed into round ones before they are mounted in the connector.
Technical data:
Diameters comply with DIN 46267 p. 2, except for sections 16 mm2 which are not subject to this standard
Materials: aluminum pipes and bars drawn in recrystallized form in EN AW-1050 A in accordance with PN-EN 573-3.
Core cross section [mm2] |
Type of ferrules |
Index |
Packing |
Bulk packaging |
Dimensions [mm] |
||
rm, sm |
[pcs] |
[pcs] |
D |
d |
L |
||
120 |
DZOA 120 |
WOZIA1200000001 |
1 |
12 |
23,0 |
14,7 |
105 |
240 |
DZOA 240 |
WOZIA2400000001 |
1 |
12 |
32,0 |
21,0 |
125 |
rm – round bunched core, sm – segmental bunched core, se – segmental solid core